Design of rogowski coil to measure the power frequency alternating current

  • Authors

    • A Benitto Vellore Institute of Technology,Vellore
    • V Indragandhi Thiagarajar College of Engineering
    • R Abarna Thiagarajar College of Engineering
    • R Raja Singh Vellore Institute of Technology,Vellore
    2018-07-26
    https://doi.org/10.14419/ijet.v7i3.15518
  • Flexible, Coil, Mutual Inductance, Electro Motive Force, Reconstruction, Alternating Current, Integrator.
  • Abstract

    For the growth of high voltage transmission power cables, it is necessary to calculate the current and voltage values. Current Transformers (CT) are used to convert the larger current values into smaller values. CT develop the convenient way of measurement in an alternating current transmission line. If CT becomes saturated then secondary current in a CT gets distorted because of a larger primary current. This distorted secondary current leads to a malfunction in the measurement side. So, detection and correction of the distorted current caused by the saturated CT becomes essential. To avoid these problems, we can use Rogowski Coil (RC) to measure the alternating current.

    RC is a toroidal coil used for measuring alternating current without touching the conductor. A RC is an evenly wound coil of N turns per meter on a nonmagnetic core of constant cross-sectional area A. Normally an alternating current produces a magnetic field when current flows through a conductor. RC is used to sense the magnetic field and rise to an induced voltage within the coil which is proportional to the rate of change of the current being measured. This RC current measurement is based on adopted reconstruction methods. In this paper, use two reconstructions methods to measure the alternating current. They are Analog integrator and Numerical Differentiation (ND). These reconstruction methods providing accurate as well as reduced time for correctly tracking the measured current.

     


  • References

    1. [1] Yu D. C., Cummins J. C., Z. Wang, H. J. Yoon and L. A. Kojovic, 2001 “Correction of current transformer distorted secondary currents due to saturation using artificial neural networks", IEEE Transaction. Power Delivery. 16 (2), pp. 189-194. https://doi.org/10.1109/61.915481.

      [2] Hajipour E., Vakilian M., and Sanaye-Pasand M., 2015 "Current-Transformer Saturation Compensation for Transformer Differential Relays", IEEE Transaction. Power Delivery. 30 (5), pp. 2293-2302. https://doi.org/10.1109/TPWRD.2015.2411736.

      [3] Hemmati E., Shahrtash S. M., Jan. 2013 "Digital Compensation of Rogowski Coil’s Output Voltage," IEEE Transaction. Instrumentation. and Measurement., 62 (1), pp. 71–82. https://doi.org/10.1109/TIM.2012.2212502.

      [4] Metwally I. A., Jan. 2014 "Novel designs of wideband Rogowski coils for high pulsed current measurement," IET Science. Measurement and Technology. 8 (1), pp. 9–16. https://doi.org/10.1049/iet-smt.2013.0045.

      [5] Kojovic L. A., 2006, "Application of Rogowski coils used for protective relaying purposes," IEEE Transaction. Instrumentation and Measurement. Pp.538–543. https://doi.org/10.1109/PSCE.2006.296371.

      [6] Mohammad Hamed Samimi, Arash Mahari, Mohammad Ali Farahnakian, Hossein Mohseni, Year: 2015, “A Review on the RCPrinciples and Applications†IEEE Sensors Journal, 15 (2), Pages: 651 – 658. https://doi.org/10.1109/JSEN.2014.2362940.

      [7] Chiampi M., Crotti G., and Morando A., Mar.2011 "Evaluation of Flexible RCPerformances in Power Frequency Applicationâ€, IEEE Transaction. Instrumentation and Measurement. 60 (3), pp.854–862. https://doi.org/10.1109/TIM.2010.2060223.

      [8] Mohamed E. Ibrahim, and Amr M. Abd-Elhady, Year: 2016, “Differential Reconstruction Method for Power Frequency AC Current Measurement Using RC“IEEE Sensors Journal, 16 (23), Pages: 8420 - 8425.

      [9] El_Kalashy N. I., Kawady T. A., Ismail E. M., and Taalab A. I., 2016 "Fundamental current phasor tracking using DFT extraction of RC signal", IET-Science Measurement and Technology, 10 (4), pp. 296-305.

      [10] Hong Y. Y. In addition, Chang-Chian P. C., 2008 "Detection and correction of distorted current transformer current using wavelet transform and artificial intelligence", Process and Instrumentation Engineering. Technol., Generation. Transmission and Distribution. Two, pp. 566575.

      [11] Ashok Kumar L; Indragandhi V; Sujith Kumar N Design and implementation of single-phase inverter without transformer for PV applications, IET Renewable Power Generation, 2018, Vol. 12 Iss. Five, pp. 547-554.

      [12] T. Arunkumari, V. Indragandhi “An overview of high voltage conversion ratio DC-DC converter configurations used in DC micro-grid architecturesâ€, Renewable and Sustainable Energy Reviews, Vol. 77, pp. 670–687, 2017. https://doi.org/10.1016/j.rser.2017.04.036.

      [13] R. Raja Singh, B. Anil Kumar, D. Shruthi, Ramraj Panda, C. Thanga Raj, “Review and experimental illustrations of electronic load controller used in standalone Micro-Hydro generating plants,†Engineering Science and Technology, an International Journal, Elsevier, 2018.

  • Downloads

  • How to Cite

    Benitto, A., Indragandhi, V., Abarna, R., & Raja Singh, R. (2018). Design of rogowski coil to measure the power frequency alternating current. International Journal of Engineering & Technology, 7(3), 1605-1608. https://doi.org/10.14419/ijet.v7i3.15518

    Received date: 2018-07-13

    Accepted date: 2018-07-16

    Published date: 2018-07-26