Control of Movement of Metallic Particles in a GIS

  • Authors

    • A. Giri Prasad
    • Poonam Upadhyay
    • M. Suryakalavathi
    • N. Karthik
    https://doi.org/10.14419/ijet.v7i4.22.28709
  • Metallic Particle contamination, Electrostatic Fields, Image Charge Effect, Dielectric Coating.
  • The analysis of motion of metallic particles in a GIB along with a control strategy is presented in this work. Metallic particle contamination is an inevitable problem that greatly impairs the performance of dielectric medium (SF6 gas) in a GIS. This can lead to a catastrophic failure of a GIS. A CIGRE study suggests that more than twenty percent failures in a GIS are caused due to metallic particle contamination. The mathematical modeling is done for a GIB to find the electric field and movement of metallic particle in the Busduct. The movement of metallic particles depends mostly upon the local electric fields in the duct. The motion of a contaminating metal particle can be greatly decreased by coating the enclosure inner surface with a Dielectric material. The results are simulated and validated by using AM and CSM methods.

     

  • References

    1. [1] J. Amarnath, S. Kamakshaiah, C. Radhakrishna, B.P. Singh and K.D.Srivastava, “Particle Trajectory in a Common Enclosure Three phase SF6 Busductâ€, 12th Intern. Sympos. High Voltage Eng., IISc, Bangalore, India, Vol. 2, pp. 441-444, 2001.

      [2] H.Anis and K.D. Srivastava, “Breakdown Characteristics of Dielectric Coated Electrodes in Sulphur Hexafluoride Gas with Particle Contami nationâ€, Sixth Intern. Sympos High Voltage Engineering, Paper No. 32.06, New Orleans, LA, USA. 1989.

      [3] A.H. Cookson, P.C. Bolin, H.C. Doepken, R.E. Wootton, C.M.Cooke and J.G.Trump, “Recent Research in the United State on the Effect of Particle Contamination Reducing the Breakdown Voltage in Compressed Gas Insulated Systemâ€, Int. Conf. On Large High Voltage System; Paris, 1976.

      [4] J .R. Laghari and A. H. Qureshi, “A review of particle contaminated gas breakdownâ€, IEEE Trans, Electr. Insul., Vol, 16, pp. 388-398, 1981.

      [5] H. Anis, K.D. Srivastava “Free conducting particles in compressed gas insulationâ€; IEEE Trans. on electrical insulation, Vol. EI-16, pp. 327- 338, Aug.1995.

      [6] M.M. Moreos, K.D. Srivastava, H.Anis “Dynamics of metallic con taminants in compressed gasesâ€, IEEE Int. Conf. On Industrial Appli cations; 1983.

      [7] G.V.Nagesh Kumar J.Amarnath, B.P.Singh, D.Srivatsava.,“Influence of Power frequency and Impulse voltages on particle movement in Gas Insulated Bus duct (GIB) with epoxy coatingsâ€. at National Seminar onInsulating materials for the Power Industry, organized by Central Power Research Institute, Bangalore during26-27 August, 2004

      [8] John H. Brunke, Hermann Koch, Revision GIS standard rated above 52 kV – C37.122, IEEE Transaction, Substation Technical Specificaions, 2010

      [9] J. Amarnath, B. P. Singh, C. Radhakrishna and S. Kamakshiah, “Determination of particle trajectory in a Gas Insulated Busduct predicted by Monte-Carlo techniqueâ€, IEEE Conf. Electr. Insul.Dielectr. Phenomena (CEIDP), Texas, Austin, USA, 1991 Vol. 1, pp. 399-402,1991.

      [10] Nazar H.Malik, “A Review of the Charge Simulation Method and its Applicationsâ€, IEEE Trans, Electr. Insul., Vol, 24, pp.3-20, 1989.

      [11] H.Singer, H.Steinbigler and P.Weiss, “A Charge Simulation Method for the Calculation of High Voltage Fieldsâ€, IEEE Power Engineering Society, 1974.

  • Downloads

  • How to Cite

    Giri Prasad, A., Upadhyay, P., Suryakalavathi, M., & Karthik, N. (2018). Control of Movement of Metallic Particles in a GIS. International Journal of Engineering & Technology, 7(4.22), 259-263. https://doi.org/10.14419/ijet.v7i4.22.28709